These specifications designate the requirements for manufacturing and installing Vinyltech AWWA C900 water pipe.
- AWWA C900-07 - Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 In. Through 12 In. (100mm Through 300mm), for Water Transmission and Distribution
- AWWA C605 - Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water
- ASTM D1784 - Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds
- ASTM D3139 - Standard Specification for Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals
- ASTM F477 - Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
- ASTM D2412 - Standard Test Method for
Determination of External Loading Characteristics of Plastic Pipe by Parallel-Plate Loading
- UNI-PUB-8 - Tapping Guide for AWWA C900 Pressure Pipe
- UNIB-8 - Recommended Practice for the Direct Tapping of PVC Pressure Water Pipe (Nominal Diameters 6-12 inch)
PIPE COMPOUND
The pipe shall be extruded from compounds meeting (PVC1120) the requirements of Cell Classification 12454-B, as defined in ASTM D 1784, Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds. The PVC shall also be listed by the National Sanitation Foundation (NSF) for use in potable water.
PIPE
Vinyltech pipe shall be manufactured in
accordance with AWWA C900-07.
GASKET JOINT
The gasket shall be reinforced with a steel band and meet the requirements of ASTM F477. Vinyltech pipe shall have an integral bell end with a locked-in factory installed gasket and shall meet the joint requirements of ASTM D3139. |
The pipe shall be marked in accordance with
AWWA C900 as in the following example.
-
Manufacturer’s name and production codes
-
Nominal size, dimension ratio number, and O.D. base (for example, 8” DR 18 CIS)
-
Materials cell classification (PVC1120)
-
AWWA pressure class (235 psi or 305 psi) and hydrostatic test pressure (T600, or T800)
-
AWWA designation number (AWWA C900-07)
-
National Sanitaion Foundation (NSF-61)
-
Production date and time code (VJHB10A 48:34)
-
FM Approvals (FM) logo, third party certification
-
Underwriters Laboratories, Inc (UL) logo, third party certification
Each length of the pipe including the bell shall be hydrostatically tested in accordance with AWWA C900-97. The pipe shall meet all additional test requirements as described in AWWA C900. Our full time quality assurance staff continually administers a rigid program of tests
to maintain the production of the best pipe products available.
Recommended installation procedure of Vinyltech Corporation and the Uni-Bell PVC Pipe Association are outlined in AWWA C605, Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water. The Uni-
Bell Handbook of PVC Pipe is also an invaluable resource guide for design and installation.
The consistent success of tapping PVC pressure pipe is contingent upon the use of proper procedures and equipment. Vinyltech recommends strict compliance with the requirements as specified in UNI-B-8, UNI-PUB-8, and AWWA C605.
Assembly of Vinyltech PVC transmission pipe is easily accomplished. A depth of entry mark is on each spigot end to serve as a visual check for rapid, accurate joint inspection. Do not over insert.
- Remove any mud, sand, or other foreign
matter from the belled and spigot ends of the
pipe. Carefully clean the gasket area.
- With a clean applicator (a brush or hand)
lubricate the entire surface of the pipe from
the spigot end to the depth of entry mark and
the contact surface of the gasket with
Vinyltech Brand Lubricant.
- Brace the bell to avoid disturbing the already
installed joints. Align the pipe, insert the
spigot into the bell and push until the entry
mark is reached. Do not insert past the
entry mark line.
|