Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight
(LB/100')

Inches

Millimeters

16

400

17.400

0.696

20

60-80

2575

 

Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight (LB/100')

Inches

Millimeters

16

400

17.400

0.967

20

60-80

3475

 

 

 

 

 

VINYLTECH AWWA C905
TECHNICAL DATA SUBMITTAL

CONFORMANCE
These specifications designate the requirements for manufacturing and installing Vinyltech PVC sewer pipe.
ASTM D 3034 - Standard Specification for Type
PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and
Fittings

  • AWWA C905-97 - Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14” Through 48”(350mm Through 1,200mm), For Water Transmission and Distribution
  • AWWA C605 - Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water
  • ASTM D 1784 - Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds
  • ASTM D 3139 - Standard Specification for Joints
    for Plastic Pressure Pipes Using Flexible Elastomeric Seals
  • ASTM F 477 - Standard Specification for
    Elastomeric Seals (Gaskets) for Joining Plastic Pipe
  • ASTM D 2122 - Standard Method of Determining
    Dimensions of Thermoplastic Pipe and Fittings
  • ASTM D 2837 - Method for Obtaining Hydrostatic
    Design Basis for Thermoplastic Pipe Materials

PIPE COMPOUND
The pipe shall be extruded from compounds meeting (PVC1120) the requirements of Cell Classification 12454-B, as defined in ASTM D 1784, Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds. The PVC shall also be listed by the National Sanitation Foundation (NSF) for use in potable water.

PIPE
Vinyltech pipe shall be manufactured in accordance with AWWA C905-97.

GASKET JOINT
The gasket shall be reinforced with a steel band and meet the requirements of ASTM F477. Vinyltech pipe shall have an integral bell end with a locked-in factory installed gasket and shall meet the joint requirements of ASTM D 3139.

MARKING
The pipe shall be marked in accordance with AWWA C905 as in the following example.

  1. Manufacturer’s name and production codes
  2. Nominal size, dimension ratio number, and O.D. base (for example, 16” DR 18 CI)
  3. Materials cell classification (PVC1120)
  4. AWWA pressure rating (PR 165, or PR 235) and hydrostatic test pressure (T/330, or T/470)
  5. AWWA designation number (AWWA C905)
  6. Production date code (VOO 101A)
  7. Seal of the testing agency that verified the suitability of the pipe and the material for potable water (NSF)

QUALITY CONTROL
Each length of the pipe including the bell shall be hydrostatically tested in accordance with AWWA C905-97. The pipe shall meet all additional test requirements as described in AWWA C905. Our full time quality assurance staff continually administers a rigid program of tests to maintain the production of the best pipe products available.

INSTALLATION
Recommended installation procedure of Vinyltech Corporation and the Uni-Bell PVC Pipe Association are outlined in AWWA C605, Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water. The uni-
Bell Handbook of PVC Pipe is also an invaluable resource guide for design and installation.

TAPPING
The consistent success of tapping PVC pressure pipe is contingent upon the use of proper procedures and equipment. Tapping should be as recommended in AWWA C605.

ASSEMBLING THE PIPE
Assembly of Vinyltech PVC transmission pipe is easily accomplished. A depth of entry mark is on each spigot end to serve as a visual check for rapid, accurate joint inspection. Do not over insert.

  1. Remove any mud, sand, or other foreign
    matter from the belled and spigot ends of the
    pipe. Carefully clean the gasket area.
  2. With a clean applicator (a brush or hand)
    lubricate the entire surface of the pipe from
    the spigot end to the depth of entry mark and
    the contact surface of the gasket with
    Vinyltech Brand Lubricant.
  3. Brace the bell to avoid disturbing the already
    installed joints. Align the pipe, insert the
    spigot into the bell and push until the entry
    mark is reached. Do not insert past the
    entry mark line.
201 South 61st Avenue • Phoenix, Arizona 85043 • Phone (602) 233-0071 • Fax (602) 272-4847
c