trans trans trans trans end  

 

Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight (LB/100')

Inches

Millimeters

4

100

4.800

0.267

16

1020

251.6

6

150

6.900

0.383

16

440

521.2

8

200

9.050

0.503

20

200

903.0

10

250

11.100

0.617

12

240

1364.4

12

300

13.200

0.733

28

60-80

1935.8

 

Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight (LB/100')

Inches

Millimeters

4

100

4.800

0.343

16

1020

317.5

6

150

6.900

0.493

16

440

658.7

8

200

9.050

0.646

20

200

1139.7

10

250

11.100

0.793

12

240

1722.3

12

300

13.200

0.943

28

60-80

2445.5

 

C905 DR 25 Pressure Rated 165

Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight (LB/100')

Inches

Millimeters

16

400

17.400

0.696

20

60-80

2575

 

C905 DR 18 Pressure Rated 235

Nominal Size

Outer Diameter (IN)

Minimum Wall (IN)

Lifts Per Truck

Feet Per Lift

Approximate Weight (LB/100')

Inches

Millimeters

16

400

17.400

0.967

20

60-80

3475

 

 

VINYLTECH PURPLE PIPE
TECHNICAL DATA SUBMITTAL

SCOPE
These specifications designate the dimensional requirements for manufacturing and installing Vinyltech’s Vinylguard Purple PVC Pipe for reclaimed water.

  • AWWA C900-97 - Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 in. Through 12 in. (100mm Through 300mm), for Water Transmission and Distribution
  • AWWA C905-07 - Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14” Through 48” (350mm Through 1,200mm) for Water Distribution
  • ASTM D 1784 - Standard Specification for Rigid
    Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds
  • ASTM D 3139 - Standard Specification for Joints
    for Plastic Pressure Pipes Using Flexible Elastomeric Seals
  • ASTM F 477 - Standard Specification for Elastomeric Seals (Gaskets ) for Joining Plastic Pipe
  • ASTM D 2122 - Standard Method of Determining
    Dimensions of Thermoplastic Pipe and Fittings
  • ASTM D 2837 - Method for Obtaining Hydrostatic
    Design Basis for Thermoplastic Pipe Material

PIPE COMPOUND
The pipe shall be extruded from compounds meeting (PVC1120) the requirements of Cell Classification 12454-B, as defined in ASTM D 1784, Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride) (CPVC) Compounds.

PIPE
Vinyltech pipe shall be manufactured in accordance
with the dimensional standards of AWWA C905 or
AWWA C900.

GASKET JOINT
The gasket shall be reinforced with a steel band
and meet the requirements of ASTM F 477. Vinyltech pipe shall have an integral bell end with a locked-in factory installed gasket and shall meet the joint requirements of ASTM D 3139.

MARKING
Vinylguard is marked with two print lines on opposite sides of the pipe. Both sides read “CAUTION RECLAIMED WATER - DO NOT DRINK” in intervals not to exceed 5 feet. Additional marking information is also applied. The UL, FM, and NSF
designations do not apply and are not printed on reclaimed water pipes.

QUALITY CONTROL
Our full time quality assurance staff continually administers
a rigid program of Vinyltech’s standard tests to maintain the production of the best pipe products available.

INSTALLATION
Recommended installation procedure of Vinyltech Corporation and the Uni-Bell PVC Pipe Association are outlined in AWWA C605, Underground Installation of Polyvinyl Chloride (PVC) Pressure Pipe and Fittings for Water. The Uni-Bell Handbook of PVC Pipe is also an invaluable resource guide for design and installation.

ASSEMBLING THE PIPE
Assembly of Vinyltech PVC transmission pipe is easily accomplished. A depth of entry mark is on each spigot end to serve as a visual check for rapid, accurate joint inspection. Do not over insert.

  1. Remove any mud, sand, or other foreign
    matter from the belled and spigot ends of the
    pipe. Carefully clean the gasket area.
  2. With a clean applicator (a brush or hand)
    lubricate the entire surface of the pipe from
    the spigot end to the depth of entry mark and
    the contact surface of the gasket with
    Vinyltech Brand Lubricant.
  3. Brace the bell to avoid disturbing the already
    installed joints. Align the pipe, insert the
    spigot into the bell and push until the entry
    mark is reached. Do not insert past the
    entry mark line.

 

201 South 61st Avenue • Phoenix, Arizona 85043 • Phone (602) 233-0071 • Fax (602) 272-4847